USTEST 2001/P UNDERFILL TEST
The Alert Model 1000 UST Test System is a mass based system for
measuring tank leakage. It uses a patented mass measurement technique
using the buoyancy force measurement of a displacement probe. Changes in
buoyancy force are directly related to changes in the mass of product in
the tank. Measuring mass change eliminates the need for correcting for
product temperature expansion and contraction. The system consists of a
displacement probe sized to the tank diameter, attached to a load cell and
inserted on the base of an existing 2 to 4 inch riser pipe. The load cell
measures changes in buoyancy force and transfers this information to a
removable, battery powered logger. This permits testing to be done without
an operator at the site. After the test is completed, the data is
downloaded to a PC for leak rate determination.
TANK CAPACITIES: Static Tank Testing up to 30,000 gallons.
TEST TIME: Static Datalogger Tests: 2 - 8 hours.
SETUP TIME: The Model 1000 setup requires approximately 30 minutes
per tank excluding any site tank modifications.
PERFORMANCE: The Model 1000 certification has been EPA third party
certified to exceed 0.1gph 95%Pd 5%Pfa specifications in tanks 20 to 95%
full.
OPENING SIZE: The 2000 series load cell installs in a 2",
3" or 4" tank opening.
USTEST 2000/U ULLAGE TEST
The Alert Model 1050 UST Ullage test system is a microprocessor
controlled test method which uses a transducer to record signals measured
in the tank during the test. The transducer is inserted in the tank
through the fill pipe or other opening and is positioned just below the
top of the tank. The tank is monitored at atmospheric pressure to
determine the background noise level. The tank is then pressurized to 1.5
PSIG, or may be depressurized to -1.5 PSIG and monitored for the sound of
air passing through an opening. The data collected by the transducer is
analyzed using digital signal processing techniques and fourier transform
analysis to declare the tank leaking or tight.
TANK CAPACITIES: The Model 1050 will test up to 24,000 gallons of
ullage space in an underground storage tank.
TEST TIME: The Model 1050 requires 10 minutes to perform a test.
SETUP TIME: The Model 1050 setup requires approximately 20 minutes
excluding any site tank or vent opening modifications.
PERFORMANCE: The Model 1050 has been EPA third party certified to
the non-volumetric protocol.
OPENING SIZE: The Model 1050 will install in a 2", 3" or
4" tank opening